beautypg.com

Delta RMC151 User Manual

Page 976

background image

RMC70/150 and RMCTools User Manual

General
This gain helps compensate for changing system dynamics, such as varying loads, and

often aids the axis in rapidly reaching the Command Position or Command Velocity. A low

gain slows the response of the axis to changes and may keep the axis from reaching the

Command Position or Command Velocity. A gain that is too high may make the axis

oscillate.
The Integral Gain controls how much of the Control Output is generated due to the

accumulated Position Error or Velocity Error while in position control or velocity control,

respectively. Position control is defined as when the Current Control Mode is Position PID.

Velocity control is defined as when the Current Control Mode is Velocity PID.
Each gain of the axis contributes to the Control Output. The contribution from the Integral

Gain is called the Integral Output Term. For both PID and I-PD, each control loop, the

Integral Gain is multiplied by the control loop time and Position Error or Velocity Error and

added to the Integral Output Term. The Integral Output term is added to the PFID

Output.
See the Tuning topic for details on how to properly adjust the Integral Gain.
The Integral Gain may be disabled or only be allowed to decrease the Integral output

Term under certain conditions. See below for more details.
Advanced: I-PD
This gain is the most important gain for I-PD control. It must be non-zero in I-PD mode.

If it is zero, it will cause a run-time error. A higher value will increase the response. A

value that is too high will cause oscillation and instability.

Special Conditions

Integrator Hold
The Integral Gain can be disabled by the user by setting the Integrator Mode to Always

Held. The Integrator Output Term will be held at the value at the time it was set.
The Integrator Hold does not apply to Position I-PD or Velocity I-PD, since the integrator

is an important part of the I-PD control.
Integrator Adjust
The Integral Output Term can be manually adjusted with the Integrator Adjust (70)

command. This is useful for clearing it if it has "wound up" for some reason. See the

Integrator Adjust (70) topic for more details.
Integral Gain is Zero
If the Integral Gain is zero, the Integral Output Term will be set to zero.
Output Limiting
When the PFID Output reaches it's maximum value, the Integral Output Term may be

reduced to limit the PFID Output. This helps to avoid overshoot. This applies to all control

modes.

Example:
If the Proportional Output Term is 60%, the Integral Output Term is 10%, the

Differential Output Term is 10%, the Velocity Feed Forward is 25%, and the

Acceleration Feed Forward is 0%, then the total is 105%. This will be limited to

100%, so the Integral Output Term will be set to 5%.

Wind-Down Only
In the Position PID control mode, the Integral Output Term will only be allowed to

decrease in the following conditions:.

Within Deadband Window

When the target is stopped, and the Position Error is less than the Deadband

Tolerance, the Integral Output Term will only be allowed to wind down. In systems

956

Delta Computer Systems, Inc.

This manual is related to the following products: