6 Communication

This window shows all settings that can be configured in the RMC. Notice that only

the 0005 Produced Data Length and 0006 Consumed Data Length

parameters are used with the Omron controllers. The producer and consumer

locations were set within RMCTools earlier in this process, and the RPI will be set

later in the process.

b.

For the 0005 Produced Data Length parameter, enter the number of registers

that you want the RMC to send cyclically to the PLC. If you chose to use the Sync

Register, then this value must include the Sync Register.

c.

For the 0006 Consumed Data Length parameter, enter the number of registers

that you want the PLC to send cyclically to the RMC. If you chose to use the Sync

Register, then this value must include the Sync Register.

d.

Click OK.

8.

Create Tag Sets for the Input and Output Data

Before establishing an I/O connection, the location for the I/O data in the Omron PLC

must be configured. The following procedure describes one way of doing this.

However, be aware that the tags must be known about both by CX-Programmer and

Network Configurator. Section 6-2-4 Creating Tags and Tag Sets of the Omron

EtherNet/IP Units Operational Manual (W465) manual describes other methods

of creating tag sets.