beautypg.com

Using automationdirect plcs with the rmc, Automationdirect plcs, Automationdirect plcs with the rmc – Delta RMC151 User Manual

Page 581

background image

6 Communication

5. Wait Until the Sync In and Sync Out Registers Match

This indicates that the RMC has received the command and issued it. It is important to

wait until the SyncIn and SyncOut match before using the status bits in the Input Data

(if the Input Data includes any status bits). See the Using an EtherNet/IP I/O

Connection topic for how problems can occur if this step is ignored.

See Using an EtherNet/IP I/O Connection for further details.
Reading and Writing other registers
To read and write other registers in the RMC that are not included in the Incoming or

Outgoing Cyclic I/O Data, you can use MSG blocks (see Using Allen-Bradley Controllers

via Message Block). EtherNet/IP I/O and MSG blocks can be used simultaneously.
Another option for writing to other RMC registers is to create user programs that move

data from the variable table to other RMC registers.
Reading DWORDs from the RMC
EtherNet/IP I/O will exchange data between the PLC and RMC as if they are all REAL

values. However, some data items are of type DWORD or DINT, such as the Status Bits

and Error Bits, which are of DWORD type. These values will not be displayed properly in

the PLC's I/O Input and Output arrays.
To view DWORD or DINT values properly in the PLC, use the COP instruction to copy them

from the Input array (:I) into a tag of DWORD type. To write DWORD or DINT values to

the RMC, use the COP instruction to write the values to the Output array (:O).

6.11.3. Using AutomationDirect PLCs with the RMC

The RMC family of controllers can communicate with AutomationDirect DirectLogic PLCs via

Ethernet or serial RS-232/485.

RMC and AutomationDirect DirectLogic PLC Compatibility
AutomationDirect
PLC

RMC75E and RMC150E

RMC75S

DL05/06

Requires H0-ECOM100

module. Use Modbus/TCP

master.

Requires D0-DCM Module. Use

Modbus/RTU master.

DL105

Not Compatible

Not Compatible

DL205

Requires H2-ECOM100

module. Use Modbus/TCP

master.

DL250-1 and DL260 support

Modbus/RTU master on the

CPU. No support for 230 and

240.

DL305

Not Compatible

Not Compatible

DL405

Requires H4-ECOM100

module. Use Modbus/TCP

master.

Not Compatible

Example Programs

Delta provides example PLC programs to help you quickly set up the communications

between your PLC and the RMC. See the downloads section of Delta's website at

www.deltamotion.com.

Communicating with the RMC75E or RMC150E

deltamotion.com

561

This manual is related to the following products: