Delta RMC151 User Manual
Page 654
RMC70/150 and RMCTools User Manual
Tolerance At 10 V: Currently unavailable
Resolution 16 bits
Output Isolation Not isolated
Overload protection One-second short-circuit duration
Overvoltage protection Outputs are protected by clamp diodes
Fault Input
Input Characteristics 12-24 VDC, sinking or sourcing
Logic Polarity True High
Input "High" Range 7 to 26.4 VDC (polarity independent)
3mA maximum
Input "Low" Range 0 to 3.5 VDC (polarity independent)
<1 mA
Maximum Propagation
Delay
100 µs
Enable Output
Output Type Solid State Relay
Logic Polarity User Selectable to Active Open or Active Closed
Isolation 500 VAC
Rated Voltage 12-24 V, max 30 V (DC or peak AC voltage)
Maximum Current 75 mA
Maximum Propagation
Delay
1.5 ms
Closed Low Impedance (50 Ω maximum)
Open High Impedance (<1 µA leakage current at 250 V)
See the Fault Input and Enable Output topics for usage details.
LEDs
Axis LED
This LED represents the input and control status for the axis. This bi-color (red/green)
LED has the following states:
State
Description
Steady
Off
No power or this input is not assigned to an axis.
Steady
Green
The axis is either in closed loop control or is a reference axis. The axis is
not halted.
Flashing
Green
The input is in open loop and the axis is not halted (not possible for
reference axes).
Flashing
Red
A Closed Loop Halt or External Halt has occurred because an error bit is set
(not possible for reference axes). The LED will not turn red due to a halt
caused by halt command.
Steady
Red
An Open Loop Halt or Direct Output Halt has occurred because an error bit
is set (for reference axes, any halt has occurred). The LED will not turn red
due to a halt caused by halt command.
En/F LED
This LED represents the status of the Enable Output and Fault Input for the axis. This bi-
color (red/green) LED will have the following states:
634
Delta Computer Systems, Inc.