10 Wiring and Installation

Daisy-Chaining Quadrature Inputs

One quadrature encoder can typically output its A and B signals to thirty-two (32) RMC70

Q1 modules. Use a daisy-chain topology as shown below. Do not use a star topology. Add

termination only to the last input, as illustrated. Incorrect termination will result in

distorted signals and will cause incorrect transducer readings.

10.3. RMC150

10.3.1. RMC150 Mounting Instructions

Mounting Options:

• Symmetrical DIN 3
• Panel-mount

Orientation:

The RMC should be mounted upright on a vertical surface, such that the air holes are on

top and bottom.

Clearance above and below:

The amount of clearance required depends on the maximum ambient temperature:

Ambient Temperature

Clearance

122 - 140°F (50-60°C)

3 in (7.6 cm)

86 to 122°F (30 to 50°C)

2 in (5.1 cm)

Less than 86°F (30°C)

1 in (2.5 cm)

Mounting Dimensions

The width depends on the number of slots in the backplane.

Width

3 Slots 4.10 in.
4 Slots 5.10 in.
5 Slots 6.10 in.
6 Slots 7.10 in.

deltamotion.com

1145