beautypg.com

Delta RMC151 User Manual

Page 1162

background image

RMC70/150 and RMCTools User Manual

Figure 1: SSR switching inductive inductive load: high-side configuration.

Example: Calculating maximum current for inductive load.
To calculate the maximum current through the SSR in the above diagram, we assume

zero SSR resistance:

Max. current = 24V / 480Ω = 50mA
Max. current = 12V / 480Ω = 25mA

In the 24V case, the maximum current is right at the maximum allowed by the SSRs. The

outputs may be overpowered if the coil resistance is reduced further. To calculate the

typical current through the SSR, we use the typical SSR resistance of 25W:
Typical current = 24V / (480Ω + 25Ω) = 47.5mA
Typical current = 12V / (480Ω + 25Ω) = 23.8mA

Discrete Inputs

The discrete inputs are compatible with signal levels ranging from 12V to 24V. Each input

draws a maximum of 2.6mA with a 12V or 24V input. Most PLC outputs can be connected

to the DI/O inputs directly. The exception is open collector (sinking) outputs. See the

discussion below for using sinking outputs.
Wiring Diagrams
The following are some input wiring diagrams:

Figure 4: Direct connection to Programmable

Controller.

Figure 5: Relay Connection from

Programmable Controller.


Using D8 Inputs with Open Collector Outputs
The D8's discrete inputs can be used with open collector (sinking) outputs. There are

three configurations that can be used to drive the D8 inputs from an open-collector

output:

1142

Delta Computer Systems, Inc.

This manual is related to the following products: