To read a plot using this method, follow these steps:
1. Wait for the Plot to Complete

Before reading the plot data using this method, the plot must have completed capturing

data. Reading the plot before it has completed may result in unusable information.
Use the Plot State register to tell whether the plot has completed capturing. The plot

has completed when the Plot State register is 2:

0 = not triggered, 1 = capturing, 2 = complete.

2. Read the Plot Data

Read the data from the Static Plot Upload Area, as listed below. For other address

formats, see the RMC70 Register Map - Static Plot Upload or the RMC150 Register Map -

Static Plot Upload topics.
Static Plot Upload Area Register

RMC150 Address

RMC70 Address

Plot 0, Data Set 0 (samples 0-4095)

%MD112.0-4095

%MD48.0-4095

Plot 0, Data Set 1 (samples 0-4095)

%MD113.0-4095

%MD49.0-4095

Plot 0, Data Set 2 (samples 0-4095)

%MD114.0-4095

%MD50.0-4095

Plot 0, Data Set 3 (samples 0-4095)

%MD115.0-4095

%MD51.0-4095

Plot 1, Data Set n (samples 0-4095),

n=0-3

%MD116+n.0-

4095

%MD52+n.0-4095

Plot 2, Data Set n (samples 0-4095),

n=0-3

%MD120+n.0-

4095

n/a

Plot 3, Data Set n (samples 0-4095),

n=0-3

%MD124+n.0-

4095

n/a

Plot 4, Data Set n (samples 0-4095),

n=0-3

%MD128+n.0-

4095

n/a

Plot 5, Data Set n (samples 0-4095),

n=0-3

%MD132+n.0-

4095

n/a

Plot 6, Data Set n (samples 0-4095),

n=0-3

%MD136+n.0-

4095

n/a

Plot 7, Data Set n (samples 0-4095),

n=0-3

%MD140+n.0-

4095

n/a

Note:

Many host controllers do not support reading files with 4096 elements. However, smaller

blocks of data can be read just as well.

Tip:

In order to use the plot data, you will probably need to know the sample period. The Sample

Period register contains that information.

Verifying that the Plot wasn't Overwritten

It is possible that while you are reading up a plot, the plot re-triggers and is

overwritten. In that case, your data may be unusable. To check whether the plot

was overwritten, compare the Plot ID register, before and after reading the plot

data.

Reading a Plot While it's Still Capturing

It is possible to begin reading up a plot before it has finished capturing. However,

reading beyond the end of the data set's currently-captured limit will result in

unusable information.

166

Delta Computer Systems, Inc.