beautypg.com

Delta RMC151 User Manual

Page 567

background image

6 Communication

The MSG block parameters differ slightly depending on the controller and programming

software. The parameters used by RSLogix 5 version 3.2.0.0, RSLogix 500 version

6.30.00, and RSLogix 5000 version 17.00.00 for the PLC-5, SLC 5/05, ControlLogix and

CompactLogix controllers respectively are described below. The SoftLogix 5 parameters

are similar.
ControlLogix and CompactLogix MSG Block Parameters
The ControlLogix or CompactLogix MSG block is displayed as follows. More detailed

information on the MSG block is available in Allen Bradley publication 1756-RM003L-EN-P,

Logix5000 Controllers General Instructions.


The Message Control portion of the MSG requires a tag.

To create a tag:

Right-click the "?" and choose NewTag.

Type a name in the Name field.

Make sure the Data Type is MESSAGE.

Click Configure. The Message Configuration dialog will open.

Enter the following on the Configuration tab:

o

Message Type: From this drop-down list, select SLC Typed Read to read

values from the RMC, or SLC Typed Write to write values to the RMC. The PLC-

5 Typed Read or Write will also work, and is required for transfers of more

than 58 registers.

o

Source Element (reads only): Enter the address of the first RMC register

you want to read. See the Registers Maps for help on addresses.

o

Source Element (writes only): Enter the tag in the ControlLogix or

CompactLogix that you want to send to the RMC. In most cases, the element

should be an array or structure composed entirely of REAL data types, since

this is the type of the RMC data.

o

Number of Elements: Enter the number of RMC registers to read or write in

this field. The ControlLogix and CompactLogix limit this to approximately 58.

For larger transfers, use the PLC-5 Typed read or write.

o

Destination Element (reads only): Enter the tag in the ControlLogix or

CompactLogix into which you want to read the RMC data. See the Source

Element bullet above for suggestions on the data type of the tag.

o

Destination Element (writes only): Enter the address of the first RMC

register you want to write. See the Registers Maps for help on addresses.

Enter the following on the Communication tab:

o

For Ethernet:

Path: Enter the path from the ControlLogix or CompactLogix CPU to the RMC.

The format of the path usually is as follows:

[Ethernet module name], 2, [RMC IP Address]

To get the Ethernet module name, click the Browse button and select the

Ethernet module. The "2" specifies the Ethernet port on the module.
Therefore, if a ControlLogix 1756-ENBT is in named LocalEnb, and the RMC

is at address 192.168.0.5, then the following path would be used:

LocalENB, 2, 192.168.0.5

deltamotion.com

547

This manual is related to the following products: