Link/Act LED
The Link/Act LED reflects the status of the physical Ethernet connection between the

RMC and the device on the other end of the Ethernet cable. If the Link LED is not on or

is not blinking when you expect it to be, see the Ethernet Link/Act LED topic for

troubleshooting information.
State

Description

Off

The Ethernet link is down

Flashing Green

The Ethernet link is up, with activity

Steady Green

The Ethernet link is up, no activity


Net LED
State

Description

Steady Off

No power, or no IP address configured.

Steady Red

Duplicate IP Address detected.

Flashing Red

IP address configured and in use, and a

controlling EtherNet/IP I/O connection has

timed out and not been re-established.

Flashing Green

IP address configured and in use, no

EtherNet/IP or PROFINET connections are

currently established, and there is no timed-out

controlling EtherNet/IP I/O connection.

Steady Green

IP address configured and in use, at least one

EtherNet/IP or PROFINET connection is

currently established, and there is no timed-out

controlling EtherNet/IP I/O connection.

Note:

The Monitor Port does not affect any LEDs on the RMC70.

Startup LED Test
When the RMC75E powers up, the LEDs listed below goes through these states, with a

250 msec delay between each step:

CPU LED

Net LED

Green

Off

Red

Off

Green

Green

Green

Red

Green

Off


Prior to the LED test, the module will run through the loader, during which time it’ll have

a Red CPU LED. After the LED test, the firmware will continue initialization, after which

time the LEDs resume their regular behaviors.

7.2.3.3. RMC75S CPU Module

624

Delta Computer Systems, Inc.