beautypg.com

Rs-485 termination and biasing – Delta RMC151 User Manual

Page 560

background image

RMC70/150 and RMCTools User Manual

19,200

3750

4000

9,600

4000

4000

4,800

4000

4000

2,400

4000

4000

6.10.3.6. RS-485 Termination and Biasing

Termination and Biasing are concepts that only apply to differential wiring. As such, they only

apply to RS-485 and not RS-232.
Note:

Delta recommends you always use biasing on a RS-485 network. To determine whether you

need termination, read the Termination Concept section in this topic.

Selecting Termination and Biasing on the RMC70

The RMC7xS termination and biasing can be independently selected with jumpers on the

8-pin RS-485 connector. The locations where the jumpers should be installed are marked

on the label.
To select termination: Insert a jumper between pins +T/R and Trm Jpr.
To select biasing:
Insert a jumper between pins SCmn and Bias Jumper.

The Termination Concept

Cable termination is a way of absorbing transmitted energy at the end of a network. This

prevents signal reflections from bouncing back towards the transmitter and potentially

upsetting signal quality and communications.
The termination resistor should match the characteristic impedance of the cable being

terminated. The effective impedance of the RMC7xS's termination resistor and biasing

resistors is 114Ω. Therefore, cabling with impedance of 100Ω to 120Ω is recommended.
Termination should be placed at the end of the network for each wire pair. For RS-485

(2-wire, point-to-point or multi-drop), terminate the wire pair at each end of the network.

The diagram in Serial Network Topologies shows the correct location of the termination.
Termination and Cable Length
Termination is not required on all differential networks, but it does typically extend the

maximum cable length. The following chart shows the maximum cable lengths at various

baud rates with and without termination:

NOTE:

The maximum cable length is the length of the entire network and not just the distance

between nodes on the network.

Termination vs. Cable Length:

Baud

Rate

Max

Unterminated

Cable Length (ft)

Termination

Requirements

Max Terminated

Cable Length

(ft)

115,200

475

Required beyond 475 ft

3250

57,600

950

Required beyond 950 ft

4000

38,400

1900

Required beyond 1900

ft

4000

19,200

3750

Required beyond 3750

ft

4000

540

Delta Computer Systems, Inc.

This manual is related to the following products: