Damping factor (simulator), Damping factor, Damping – Delta RMC151 User Manual

Page 966: Factor

background image

RMC70/150 and RMCTools User Manual

where
A = area of the piston (in

2

)

mass = the mass moved by the system (lb)
volume = the volume of trapped oil in the cylinder (in

3

)

Range

The Natural Frequency must be less than or equal to the control loop time frequency

divided by 4:

Control Loop

Time

Max Natural

Frequency

0.5 ms

500 Hz

1 ms

250 Hz

2 ms

125 Hz

4 ms

62.5 Hz

Changing this Parameter

For best results, always change this parameter only from Axis Tools. If the axis is in

Simulate mode, and this parameter is changed, simulate model will be suspended until

the last simulate mode parameter register (Max Compression [Fx:127]) has been

updated. At this point, the new simulator model will be calculated and the simulator

model will be activated. When the simulator model is suspended, the Actual Position will

not move.
Certain simulator settings may result in an invalid model. If this occurs, change your

settings. See the Simulating Motion topic for more details.

9.2.2.3.4. Damping Factor (Simulator)

Type: Axis Parameter Register

RMC70 Address: %MDn.119, where n = 12 + the axis number

RMC150 Address: %MDn.119, where n = 24 + the axis number

System Tag: _Axis[n].DampingFactor, where n is the axis number

How to Find: Axes Parameters Pane, All tab: Simulate

Data Type: REAL

Units: pu/sec

2

Range: [0..2]

Default Value: 0.75

Description

This parameter is used with a 2nd order simulator. For details on using simulate mode,

see the Simulate Mode topic.
The damping factor is a unitless number that specifies how much friction there is in the

system. Hydraulic systems typically range from 0.3 to 0.8. If the load has a lot of friction,

this value will become larger. A lower value makes the system more difficult to control.

Changing this Parameter

For best results, always change this parameter only from Axis Tools. If the axis is in

Simulate mode, and this parameter is changed, simulate model will be suspended until

the last simulate mode parameter register (Max Compression [Fx:127]) has been