beautypg.com

Fins/udp, Fins/udp, csp or df1 over ethernet, E fins/udp – Delta RMC151 User Manual

Page 451

background image

6 Communication

The RMC handles incoming packets on a first-in first-out (FIFO) basis, making it

possible to send multiple requests and then wait for the replies.

The RMC can handle up to 64 open TCP/IP connections at once. Typically each device

uses one connection at a time, allowing the RMC to be connected to up to 64 devices

at once.

Multiple-register reads and writes are limited to 100 16-bit words for writes and 125

16-bit words for reads—per the Modbus/TCP specification—even though the length

field in the Modbus/TCP header makes it look like larger packets would be supported.

Floating point numbers are 32-bit values and use two (2) holding registers each. The

least significant 16 bits comes first.

6.8.10.2. CSP

This is a proprietary protocol developed by Allen-Bradley, Inc. Variants of this are used on

Allen-Bradley's SLC 5/05 and PLC-5 controllers. This protocol is also used by the Allen-

Bradley's SoftLogix 5 and RSLinx and SoftPLC Corporation's SoftPLC. Allen-Bradley does not

publish the specifications for this protocol.
The CSP protocol is also known as "DF1 over Ethernet". It uses the same addressing format

and function code types as the serial DF1 protocol. This common component is called PCCC.
CSP can be used to read and write any registers in the RMC. In the Allen-Bradley PLCs, MSG

(message) blocks are used to read and write any registers in the RMC using CSP. See Using

Allen-Bradley Controllers via Message Block for details.

Supported PCCC function codes:

Diagnostic Status (06 03)

Echo (06 00)

SLC Protected Typed Logical Read with 2 Address Fields (0F A1)

SLC Protected Typed Logical Read with 3 Address Fields (0F A2)

SLC Protected Typed Logical Write with 2 Address Fields (0F A9)

SLC Protected Typed Logical Write with 3 Address Fields (0F AA)

PLC5 Typed Read (0F 68)

PLC5 Typed Write (0F 67)

PLC5 Word Range Read (0F 01)

PLC5 Word Range Write (0F 00)

Addressing:

Same as DF1 (serial) - see the DF1 Addressing topic.

6.8.10.3. FINS/UDP

The FINS/UDP protocol is an Omron protocol which can be used by a PLC program to transfer

data and perform other services with a remote PLC connected on an Ethernet Network. The

FINS protocol allows Omron PLCs to communicate with the RMC75E or RMC150E. The RMCs

support FINS/UDP.
The FINS/UDP protocol is an open application protocol developed and used by Omron

Electronics Inc. This protocol is available over a number of media, including Ethernet and

serial. Additional information is available in the CS1 Communications Reference Manual,

available on Omron's web site: http://www.omron.com/oei.

deltamotion.com

431

This manual is related to the following products: