Rmc75p wiring, Aa wiring, Rmc75p wiring 1 – Delta RMC151 User Manual
Page 1151: Aa wiring 1, Rmc75p
10 Wiring and Installation
10.2.4. RMC75P Wiring
The RMC75P CPU module contains a connector for power, and two connectors for
communications.
Wiring Power
The connector screws and wire clamp screws must be tightened to max 7 b-in (0.8Nm).
Wiring the Communications
RS-232 Monitor Port
For wiring the RS-232 Monitor Port, see the RS-232 Wiring for the RMC70 topic.
9-Pin PROFIBUS-DP Connector
This connector is the standard PROFIBUS connector. It is used for connecting the RMC70
to other PROFIBUS-DP devices via a standard PROFIBUS-DP cable. The pin assignment is
defined by the PROFIBUS specification.
10.2.5. AA Wiring
The AA axis module can be wired to voltage or current feedback transducers. The AA module
also a Fault input, Enable output, and a Control Output. If the AA module has two axes, each
axis' pin-out is identical.
Use shielded twisted pairs for all connections to inputs and outputs. Route the transducer
wiring separate from other wiring. You must provide the power supplies needed by your
transducers. See Wiring Guidelines for general wiring information.
Wire clamp screws must be tightened to max 7 b-in (0.8Nm).
NOTE:
The example schematics do not include transducer pin numbers, color codes, or power supply
requirements, since these vary between different transducers. To determine your power
supply needs and connector pin-outs or cable color codes, consult your transducer
manufacturer's documentation.
Pin-Out
Pin
#
AA1 Label
AA2 Label
Function
1
+Fault In
Flt In+
Fault Input
2
-Fault In
Flt In-
3
+Enable Out
En Out+
Enable Output
4
-Enable Out
En Out-
5
Control Out
Ctrl Out
Control Output
deltamotion.com