beautypg.com

Delta RMC151 User Manual

Page 1167

background image

10 Wiring and Installation

The current rating depends on the size of the backplane:

Backplane

Slots

Maximum

Current

3

375mA

4

500mA

5

625mA

6

750mA

The Case pin is electrically connected to the RMC100 case.

Discrete Outputs

The RMC150E CPU module discrete outputs are solid state relays. When they are ”off”

they have high impedance, and when ”on” they have low impedance (50Ω maximum,

25Ω typical). The user must power the outputs externally. The maximum current and

voltage for the outputs is 75 mA (50 mA for Class I, Div 2) and 30 V.
Each output has a ”+” and ”-” connection. Outputs can be wired in either a high-side or

low-side configuration.


When switching inductive loads, place a diode or tranzorb across the load to protect the

switch when transitioning from an ”on” to an ”off” state. Otherwise, the collapsing

magnetic field can cause a reverse voltage spike in excess of the 30 V rating of the Solid

State Relay.
See the RMC150 DI/O Module Wiring topic for a complete discussion of input wiring.

Discrete Inputs

The RMC150E module inputs are compatible with signal levels ranging from 12 to 24VDC.

The discrete inputs draw 3mA maximum.

deltamotion.com

1147

This manual is related to the following products: