RMC70/150 and RMCTools User Manual

Start-Once (1)

Added to curve store, but will not be saved to flash. This curve will be deleted

automatically as soon as an interpolation of this curve has been started, but the curve

will continue to be executed correctly. Start-Once curves will not be included in the

upload or download in the Curve Tool, but can be viewed in the Curves In Controller

window.

Complete-Once (2)

Added to curve store, but will not be saved to flash. This curve may be deleted

manually, but will also be deleted automatically once an interpolation of this curve has

been started and completed to the end of the curve (indicated by when the Target

Generator Done bit turns on). Complete-Once curves will not be included in the upload

or download in the Curve Tool, but can be viewed in the Curves in Controller window.

Notice that if the Life Cycle is set to Complete-Once, but the curve is run with infinite

cycles (Cycles = 0), the curve will never complete and therefore, will not automatically

delete.

Permanent (3)

Added to curve store, and will be saved to Flash when Flash is updated. Must be

manually deleted. Permanent curves will be included in the upload or download in the

Curve Tool.

Specifying a Register Address

When issuing this command from anywhere other than RMCTools, the addresses in the

Curve Data command parameter must be entered as an integer value.
RMC addresses are represented in IEC format as:

%MDfile.element, where file = file number, and element = element number.

Use the following equation to convert a register address to integer format, N:

N = file * 4096 + element


Example:
Register address %MD8.33 is 8*4096 + 33 = 32801.

8.4.7.7. Command: Curve Delete (83)

Firmware Requirement: 2.40 or newer

Hardware Limitations: RMC75S: versions 2.1D or newer only

RMC75P: versions 2.1E or newer only
RMC75E: No limitations
RMC150E: No limitations


See the Commands Overview topic for basic command information and how to issue

commands from PLCs, HMIs, etc.

Command Parameters

# Parameter Description

Data Type

Range

1 Curve ID

Internal:

DINT
External:

REAL

0-50000

2 Curve Count

Internal:

>0

768