beautypg.com

Delta RMC151 User Manual

Page 1184

background image

RMC70/150 and RMCTools User Manual

Figure 8: Open Collector Outputs to UI/O Inputs with Input Common Connected to Vcc.

Figure 9: Open Collector Outputs to UI/O inputs with input common connected to

ground. Typically not recommended due to the required external resistors and a

continuous current draw, and the fact that the logic becomes inverted. May be necessary

for mixing sourcing and sinking outputs.
For 24VDC power, the pull-up resistor should be a 4.7kΩ, ¼ watt resister. The output

must be capable of switching 2.6mA when closed. When the open collector output is

open, the DI/O input sees 11.8V @ 2.6mA.
For 12VDC power, the pull-up resistor should be a 1 kΩ, ¼ watt resister. The output must

be capable of switching 2.6mA when closed. When the open collector output is open, the

DI/O input sees 9.4V @ 2.6mA.

UI/O Quadrature Channel

Channels configured as Quadrature inputs should be wired as follows.

The A and B inputs interfaces only to 5V differential line driver (RS-422) signals. Higher

voltages will require a signal converter, available from 3rd party suppliers. Single-ended

(TTL) transducers are not supported due to low noise immunity. Always use twisted-pairs

1164

Delta Computer Systems, Inc.

This manual is related to the following products: