0

none

1

Fault Input

2

-

3

-

4

%IX0

5

%IX1

6

%IX2

7

%IX3

8

%IX4

9

%IX5

10

%IX6

11

%IX7

12

%IX8

13

%IX9

14

%IX10

15

%IX11

See the MDT/SSI Configuration Register for details about the register containing these

bits.

9.2.2.2.23.11. SSI Overflow Mode

Type: Axis Parameter Register

RMC70 Address: %MDn.10/4-6, where n = 12 + the axis number

RMC150 Address: %MDn.10/4-6, where n = 24 + the axis number

System Tag: _Axis[n].MDTSSICfg.SSIOverflowMode

How to Find: Axes Parameters Pane, All tab: Feedback

Data Type: Bits - see below

Description

This parameter is valid only on axes with SSI feedback. This parameter selects which, if

any, SSI value causes the Transducer Overflow error bit to turn on. For linear SSI axes,

choose from the options listed below. On rotary SSI axes, this parameter must be set to

None, since all SSI values are valid.

None

No transducer overflow error is ever triggered.

Zeros

A transducer overflow is triggered if all the bits in the SSI value from the feedback are

zero.

Ones

A transducer overflow is triggered if all the bits in the SSI value from the feedback are

ones.

Bit 21

A transducer overflow is triggered if bit 21 is 1.

Format Details

932