beautypg.com

Delta RMC151 User Manual

Page 622

background image

RMC70/150 and RMCTools User Manual

7. In the Properties - PN-IO (X1) dialog box, select the IO Cycle tab:

Under Update Time, select an update time between 2.0 ms and 512.0 ms. A

commonly-used update time is 16.0 ms.

Under Watchdog Time, the default number of update cycles should typically be

selected, which is 3 in this case.

8. To select the length of the Input Data—which corresponds to the Outgoing Cyclic I/O

Data area in the RMC—expand the Inputs folder in the Hardware Catalog under the

device you added to the PROFINET network, and drag the desired module onto slot 1

in the RMC’s slot view.

Notice that at the time of this writing (September 2010), Siemens S7 PLCs are limited

to 63 input registers.

602

Delta Computer Systems, Inc.

This manual is related to the following products: