beautypg.com

Delta RMC151 User Manual

Page 530

background image

RMC70/150 and RMCTools User Manual

Seven (7) contiguous registers in the RMC70 can be explicitly written or read.

See Read Any Contiguous RMC70 Registers and Write to Any Contiguous

RMC70 Registers below.

Commands can be issued to any number of axes simultaneously.

See Command Block, Issue a Single Command, and Issue Simultaneous

Commands below.

PROFIBUS bandwidth used: 2 blocks each of 16 consistent I/O words (16 bits each).

RMC70 Register Addresses for PROFIBUS

When communicating over PROFIBUS, the RMC70 registers addresses use the same

file:element addresses as the RMC70 IEC-61131 addresses.
For example, to read the Axis 0 Actual Position via PROFIBUS, notice that its address is

%MD8.8. Therefore, the address via PROFIBUS is file 8, element 8.

Parameterization

Enhanced mode requires the PROFIBUS configuration and parameterization listed below.

The GSD file does direct the PROFIBUS master setup software to automatically set up

these values, but Delta has found several cases where it is not supported correctly or

manual setup is otherwise required.

Configuration: FF FF
Parameters:

Prm_Data (bytes 1-7): See the PROFIBUS DP specification for details.
User_Prm_Data (bytes 8-14): 00 00 00 xx* 01 08 08

* The xx parameter can be 00 or 01 and selects whether the least-significant word

comes first (00) or most-significant word comes first (01).

Data Blocks

The Enhanced mode uses two fixed-length blocks of data: the Command Block and the

Response Block.
Command Block
The Command block is a block of 16 contiguous 32-bit output registers. These registers

are sent from the PLC or PC to the RMC.

The Command Block has the following structure:

Register
Number

Data
Type


Description

Command Area:

Registers 0 - 5 are used for issuing commands to the RMC70. See

Issue a Single Command and Issue Simultaneous Commands

below for details on using these registers.

0

Integer Command Register

Bit

Bit Description

31

Command Request

30

Deferred Command

29

Deferred Command

20-28 Reserved
19

Axis 3 Select

18

Axis 2 Select

510

Delta Computer Systems, Inc.

This manual is related to the following products: