10 Wiring and Installation

Typical current = 24V / (480Ω + 25Ω) = 47.5mA
Typical current = 12V / (480Ω + 25Ω) = 23.7mA

UI/O Discrete Inputs

The UI/O points configured as inputs use the Input Common and are compatible with

signal levels ranging from 12V to 24V. Each input draws a maximum of 2.6mA with a

12V or 24V input. Most PLC outputs can be connected to the UI/O inputs directly.
Because the I/O points share a single common, the inputs must all be connected to the

same type of output (sinking or sourcing). If your application has various types of

outputs, see figure 9 to convert a sinking output to a sourcing output.
Wiring Diagrams
The following are some input wiring diagrams:

Figure 4: Direct connection to the input.

Figure 5: Direct connection to Programmable

Controller.

Figure 6: Relay Connection from

Programmable Controller.


Using UI/O Inputs with Open Collector Outputs
The UI/O's discrete inputs can be used with open collector (sinking) outputs. There are

three configurations that can be used to drive the UI/O inputs from an open-collector

output:

Figure 7: PNP Configuration: This configuration is the most popular for open collector

PNP outputs.