beautypg.com

Delta RMC151 User Manual

Page 506

background image

RMC70/150 and RMCTools User Manual

On the File menu, click New. If you have multiple networks installed you will

need to then select the network type: select PROFIBUS. If you are not given the

option of selecting PROFIBUS, you may not have installed the PROFIBUS driver for

SyCon.

On the Insert menu, click Master. Move the cursor to the top device slot in the

window area (the cursor will change to an arrow with an M next to it), and click to

place the master device.

In the Insert Master dialog, select the desired master and click the Add>>

button. Enter the station address, and click OK.

On the Settings menu, click Bus Parameter.

In the Bus Parameter dialog, set the Baud Rate to the desired rate. The RMC is

capable of speeds up to 12000kBits/s (12MBaud); check the rates supported by

your master and other slaves. Click OK.

4. Add the GSD file to your configuration programs GSD database.

You must first have an open PROFIBUS project file.

On the File menu, click Copy GSD.

In the Open dialog, navigate to the directory where the DELT07E1.GSD file is

located (by default it is installed in the main RMCTools directory)

o

RMC75P: DELT07E1.GSD

o

RMC150E PROFIBUS: DELT0AC6.GSD

Select the file and click Open.

NOTE:

Depending on the version, this may not add the bitmap file. If you wish to use

the bitmap file; copy the DELTR70N.BMP or DELTR15N.BMP file to the

Fieldbus\Profibus\BMP directory under the SyCon directory (by default, the

total path will be C:\Program Files\Hilscher

GmbH\SyCon\Fieldbus\Profibus\BMP).

5. Add an RMC Motion Controller slave device to the network.

On the Insert menu, click Slave. Move the cursor to the next available device

slot in the window area (the cursor will change to an arrow with an S next to it),

and click to place the device.

In the Insert Slave dialog, click RMC75P Motion Controller or RMC150E

Motion Controller, and then click the Add>> button. Enter the station address,

and click OK.

6. Configure the RMC Slave Device.

This involves selecting the correct configuration module for your RMC module and

application. Refer to the sub-topics Determining the Appropriate GSD Configuration

Module in the PROFIBUS Configuration topic for details on selecting the correct

configuration module.

Right-click on the RMC slave device icon, and click Slave Configuration from the

shortcut menu.

In the Slave Configuration dialog, from the list of order numbers, select the

configuration module you selected in the previous steps.

Click Append Module.

You may change the I Addr. and O Addr. fields for the added module to set the

offsets of the data.

Click Parameter Data, and then Common. Select LSW First or MSW First and

click OK. Because PROFIBUS-DP does not specify the word order for 32-bit

values, we allow the order to be swapped through this setting. You will probably

not know which is correct until later in the process. If you receive data over the

486

Delta Computer Systems, Inc.

This manual is related to the following products: