Delta RMC151 User Manual
Page 577
6 Communication
6. Fill in the fields in this dialog box as follows:
Name: Type a valid module name for the RMC.
Description: Type a description.
Comm Format: Select Data - REAL.
Address/Host Name: Choose IP Address and enter the IP Address or host
name of the RMC. The RMC must have its IP address set up to match this
address.
Input: Set the Assembly Instance to 1 and set the Size to the number of
registers to transfer. If you selected to use the Sync Register, the Size should be
one plus the number of registers of the RMC's Outgoing Cyclic I/O Data.
Output: Set the Assembly Instance to 2 and set the Size to the number of
registers to transfer. If you selected to use the Sync Register, the Size should be
one plus the number of registers of the RMC's Incoming Cyclic I/O Data.
Configuration: Set the Assembly Instance to 4 and set the size to 0.
7. Click Next. The following dialog box will be displayed:
deltamotion.com
557