beautypg.com

Using serial communications, Configuration and wiring, Line drivers: rs-232/485 – Delta RMC151 User Manual

Page 553: Using, Serial communications, E using serial communications

background image

6 Communication

6.10.2. Using Serial Communications

Serial RS-232 or RS-485 communication is only available on the RMC75S, and the Monitor

port of the RMC75P.
Communicating via serial RS-232 or RS-485 from a PLC or HMI to the RMC70 consists of the

following:

Reading RMC Registers

Writing to RMC Registers

Issuing Commands

This topic describes the basics of doing this with serial communications. All data in the RMC is

stored in registers. Therefore, to communicate is to write to and read from registers in the

RMC.
For information on setting up serial communications, see the Serial Overview topic.

Reading and Writing RMC Registers

To read from or write to RMC registers, simply write to the address of the register. The

exact method will vary depending on the host controller you use, but the concept is the

same.
Finding Addresses of RMC Registers
Use any of the following methods to find the address of a register in the RMC:

Use the Register Map topic. This topic lists all the user-accessible registers in the RMC.

Make sure you use the correct address format for your communication protocol.

Use the address that is displayed in RMCTools. Many editors and windows in RMCTools

display the address of the registers. Make sure you use the correct address format for

your communication protocol.

Issuing Commands

See the Issuing Commands topic.

Reading Plots

For details on reading plots from the RMC, see the Reading Plots with a Host Controller

topic.

6.10.3. Configuration and Wiring

6.10.3.1. Line Drivers: RS-232/485

Port 1 on the RMC75S module supports two different line drivers: RS-232 and RS-485 (2-wire

only). The RMC75S Monitor Port (port 0) supports only RS-232. See the Configuring Serial

Communications topic for instructions on how to choose a line driver for port 1.

Features

The following chart compares these line drivers as implemented on port 1 of the RMC75S:

RS-232

RS-485(2-wire)

Duplex

Full

Half

Differential? No

Yes

Topology

Point-to-point Point-to-point, Multi-drop

deltamotion.com

533

This manual is related to the following products: