RMC70/150 and RMCTools User Manual

Required
(16-bit

words)

consistent**

I/O words

consistent**

I/O words

+

16

consistent**

Input words

of 16

consistent**

I/O words

16

consistent**

I/O words

+

16

consistent**

Input words

*For commands with more than 5 command parameters, only the first 5 parameters will

be issued. The remaining parameters will be 0. To issue such commands completely,

include them in a user program and issue a command via PROFIBUS to start the user

program.
**A block of PROFIBUS data is called 'consistent' if it is consistent over the length of the

block, rather than just over a single 8- or 16-bit data item. Consistent blocks of data

will stay together through the communication, from the time it was captured in the slave

device until it is delivered to the master application, whereas data from different

consistent blocks could have been sampled at different times.

For details on reading, writing and issuing commands, see the mode type you are using.

For instructions on how to select a mode, see the PROFIBUS Configuration topic.

RMC Register Addresses for Basic/Enhanced Modes

When using the Basic/Enhanced modes, the RMC register addresses use the same

file:element addresses as the RMC's Allen-Bradley IEC-61131 addresses.
For example, to read the Axis 0 Actual Position via PROFIBUS, its address is %MD8.8.

Therefore, the address via PROFIBUS is file 8, element 8.

6.9.5.2. PROFIBUS Mode: Basic

The Basic mode is one of the Basic/Enhanced PROFIBUS Modes available only on the RMC75P.

Most users will prefer the I/O Modes instead.

Features

This mode has the following features:

Eight (8) user-selectable cyclic read registers are continuously read for instant access

by the PLC or PC.

See Response Block and Setting up the Indirect Data Map below.

One (1) register anywhere in the RMC70 can be explicitly written or read.

See Read from the RMC70 and Write to the RMC70 below.

Commands can be issued to any number of axes simultaneously.

See Command Block, Issue a Single Command and Issue Simultaneous

Commands below.

PROFIBUS bandwidth used: 16 consistent I/O words (16-bits each)

RMC70 Register Addresses for PROFIBUS

When communicating over PROFIBUS, the RMC70 registers addresses use the same

file:element addresses as the RMC70 IEC-61131 addresses.
For example, to read the Axis 0 Actual Position via PROFIBUS, notice that its address is

%MD8.8. Therefore, the address via PROFIBUS is file 8, element 8.

Parameterization

Basic mode requires the PROFIBUS configuration and parameterization listed below. The

GSD file does direct the PROFIBUS master setup software to automatically set up these

492

Delta Computer Systems, Inc.