beautypg.com

Ssi fundamentals – Delta RMC151 User Manual

Page 208

background image

RMC70/150 and RMCTools User Manual

Pulse Width Modulated Transducer

The value obtained from the PWM or Start/Stop counter is put in the Raw Counts register

for that axis. The Raw Counts are converted to Counts and then into an Actual Position in

user-defined units.

Recirculations

Delta does not recommend using recirculations on MDT transducers. Recirculations have

historically been used to gain more accuracy in the measurement. However, with faster

counters on the controller, recirculations have become less important. In addition, the

highest accuracies are only available for MDT transudcers with SSI ouput, which don't

have any recirculation options.

Transducer Lengths

An MDT transducer takes a certain amount of time to determine its position. The time it

takes increases with position. Therefore, the length of the transducer dictates the

minimum Loop Time you can use.
The approximate formula for determining the maximum transducer length for a given

loop time is as follows:

Length(in.) = (LoopTime(ms) - 0.22)/0.0095

Using the formula, the following are maximum lengths for a given loop time. This

assumes no recirculations.

Loop Time

Maximum MDT Transducer Length

500µs

29.4 inches

1000µs

82.1 inches

2000µs

187.3 inches

4000µs

397.9 inches

3.12.2. SSI Fundamentals

Synchronous Serial Interface (SSI) is a widely accepted controller interface. Position data from

the sensor is encoded in a binary or Gray Code format and transmitted over a high-speed

serial interface.
Important!

The RMC SSI inputs require RS-422 (5V differential) SSI inputs. They do not support single-

ended SSI inputs or higher voltage inputs.

SSI feedback is supported by the following modules:

RMC70: MA axis module

188

Delta Computer Systems, Inc.

This manual is related to the following products: