beautypg.com

Delta RMC151 User Manual

Page 119

background image

3 Controller Features

Allows inner loop to handle non-linear valve and other final control element problems.

Allows operator to directly control inner loop during certain modes of operation (such as

startup).

Allows controller to respond quickly to the faster inner loop.

Cascade Control Disadvantages

Cost of measurement of the secondary variable (assuming it is not measured for other

reasons).

Additional complexity.

Requirements for Cascade Control:

Inner loop system dynamics must be significantly faster (such as four times faster) than

the outer loop system dynamics. If the inner loop is not faster than the outer loop, then

the cascade will not offer any significant improvement in the system control.

Inner loop must have influence over the outer loop.

Inner loop must be measured and controllable.

Using Cascaded Loops in the RMC

Setting up Cascaded Loops
Setting up cascade control in the RMC involves the following steps:

1. Define Each Loop As an Axis

Each loop of the cascade control must be defined as an axis.

a. For the inner loop, define a standard Control axis.
b. For the outer loop, define a Cascading Outer Loop axis. This axis type provides

a virtual Control Output, but does not use a physical Control Output. If you

have more than two loops, all loops except the inner loop should be Cascading

Outer Loop axes.

2. Set up and Tune Inner Loop Axis

Set up the inner loop axis as normal, including setting the Scale/Offset and tuning.

3. Tie Output of Outer Loop to Input of Inner Loop

Use gearing to tie the output of the outer loop to the input of the inner loop. If the

inner loop is position, use the Gear Absolute (25) command. If the inner loop is

pressure or force, use the Gear Absolute (Prs/Frc) (59) command. Set the Gear

Absolute command parameters as listed below. You will also need to use the Transition

Rate (56) or Transition Rate (Prs/Frc) (64) command together with the Gear Absolute

commands.

a. The Master Register command parameter should be set to the PFID Output

of the outer loop axis.

b. The Master Point A and Master Point B command parameters should be set

to -100 and 100, respectively. This is because the PFID output ranges from -

100% to +100%.

c. The Slave Point A and Slave Point B command parameters should be set to

the minimum and maximum values that you want the inner loop axis to

control to. For example, if the inner loop is a valve spool that you want to

allow to travel from 0 to 0.5 inches, set the Slave Point A and Slave Point B

command parameters to 0 and 0.5, respectively.

d. Set the Endpoint Behavior command parameter to Truncate.

If the inner loop is velocity, use the Gear Vel (Clutch by Time) (31) command, with

the Master Register as described in item a above. The Denominator should be

set to 200, and the Numerator should be set to the velocity range of the inner

axis.

deltamotion.com

99

This manual is related to the following products: