beautypg.com

Acceleration filter type, E acceleration filter type, R acceleration filter type – Delta RMC151 User Manual

Page 927

background image

9 Register Reference

Filtering makes the plots look cleaner.

Filtering can be used to "smooth" the velocity of a reference input.

Filtering the input can reduce noise in the feedback which may improve system control.

9.2.2.2.20.4. Acceleration Filter Type

Type: Axis Parameter Register

RMC70 Address: %MDn.9/15-16, where n = 12 + the axis number

RMC150 Address: %MDn.9/6-7 , where n = 24 + the axis number

System Tag: _Axis[n].PriInputBits.AccelFilterType, where n is the axis number

How to Find: Axes Parameters Pane, All tab: Feedback → Filtering/Modeling

Data Type: Bits

Range: Status Only (0), Low-Pass (1), Model (2)

Default Value: Status Only (0)

Description

This parameter specifies how the Actual Acceleration Filter is used by the RMC:

Status Only (default setting)

The Actual Acceleration Filter applies only to the Actual Acceleration status register.

The control algorithm uses the unfiltered acceleration.

Low-Pass

The Actual Acceleration Filter applies to both the Actual Acceleration status register

and the acceleration value used by the control algorithm. If you want the filter to

apply to the control, choose this option.

Model

The Actual Acceleration Filter is not used. Instead, the Model is used to calculate the

Actual Acceleration. This value is then used for both the Actual Acceleration status

register and the control algorithm. This option is only available if the Model Order

parameter is defined.

Notice that the model will be used only if a valid model can be calculated. See the

modeling topic for details.

For best control, if you select Low-Pass or Model, then you should also select the same for

the Velocity Filter Type and ensure that the Actual Position filter, Actual Velocity Filter,

and Actual Acceleration filter are the same values.

Format Details

This section is primarily for addressing the Acceleration Filter Type parameter when

communicating with the RMC from an external device. This information is not necessary

when configuring this parameter in RMCTools.

RMC70

Bit

16

Bit

15

Value

Filter

Type

0

0

0

Status

Only

0

1

1

Low-Pass

1

0

2

Model

RMC150

Bit

7

Bit

6

Value

Filter

Type

0

0

0

Status

Only

0

1

1

Low-Pass

1

0

2

Model

deltamotion.com

907

This manual is related to the following products: