1 = Slave - Clock is an
input
F144+n:17 73741
+512 x n
E1_08204
+512 x n
DWORD %MD144+n.17 DWORD Read/Write Channel 0 SSI Options
Applies only to SSI
Output and SSI Register
Input modes]
Bit 0-5 - SSI Data Bits
Range: 8-32
Bit 6 - SSI Encoding
0=Binary, 1=Gray Code
Bit 8 - Terminate
Inputs
[Applies to all SSI Output
and SSI Register Input
modes except SSI Output
- Master.]
SSI Register Input -
Standard: Data Inputs
SSI Register Input -
Monitor: Clock/Data
Inputs
SSI Output - Slave: Clock
Inputs
Bit 16-31 - SSI Clock
Rate (kHz)
Specifies the clock rate in
kHz. The actual rate will
be determined by the
available integer divisor
(16500/SSIClockRatekHz-
1). Initial supported
values are 250, 500, and
971, with the default of
250 kHz.
F144+n:18 73743
+512 x n
E1_08206
+512 x n
DINT
%MD144+n.18 DINT
Read/Write Channel 0 Wire Delay
[Applies only to SSI
Register Input modes]
Time to delay (ns) from
Clock to Data. This value
will be converted to the
nearest time delay that
can be represented with
[1..8] * [0..31] / 33MHz.
F144+n:19 73745
+512 x n
E1_08208
+512 x n
DWORD %MD144+n.19 DWORD Read/Write Channel 0 Source/Dest
[Applies only to SSI
Output and SSI Register
Input modes]
For SSI Output mode,
this is the address of the
register to send out the
SSI Output. Ignored if
Echo is enabled. For SSI
Register Input, this is the
1122