4.15. Event Log

4.15.1. Event Log Monitor

To access this dialog:

In the Project Pane, double-click Event Log.

The Event Log Monitor is one of your most important troubleshooting tools. The Event Log

Monitor displays all events that have occurred in the controller, such as issued commands,

changed parameters and errors. The Event Log Monitor is an important aid in troubleshooting.

It can be used to:

Determine whether a command was successfully issued. The entire command, with

parameters, is displayed.

Find out which, if any, error occurred.

Determine where a command was issued from, for example, from a PLC, from a User

Program, from the Command Tool.


Each entry in the Event Log Monitor has the following components:
Component Description

#

The number is solely for indicating the order of the events.

Time

The time the event occurred is given in the following format: dayd

hour:minute:second:millisecond

The time is measured from when the RMC was last powered up, and is not

a precise time. For troubleshooting, this same time can be displayed in

plots and is useful in matching events with the plot data. In the Plot

Manager, on the View menu, choose Show Absolute Time. The Plot

Detail window will include the absolute time of the cursor in the currently

displayed plot.

Event

Describes the type of event.

Details

Provides additional details on the event, such as the previous and changed

values, command source, etc


The Event Log itself is in the RMC. The Event Log Monitor simply displays the RMC's Event Log.

On the RMC75E and RMC150E, the Event Log will hold up to 8192 entries. When the maximum

number of entries is reached, the oldest entries will disappear.
On the RMC75P and RMC75S, the Event Log is limited to the lesser of 512 entries or 2048

total words. When the maximum number of entries is reached, the oldest entries will

disappear. Notice that if the Event Log Monitor is open and online with the RMC, it will store up

to 8192 entries, even though the RMC75P and RMC75S store less.

Clearing the Event Log

To clear the Event Log, click the Clear Event Log button on the toolbar in the Event

Log window. This will remove all the entries from the Event Log.