3 Controller Features
•
•
Enter Pressure/Force Control (Auto) (44)
•
Enter Pressure/Force Control (Time) (45)
•
•
•
Change Target Parameter (Prs/Frc) (81)
•
•
Curve Start Advanced (Prs/Frc) (89)
Exiting Pressure or Force Control
To exit pressure or force control, issue an open-loop or closed-loop motion command. An
Open Loop Halt or Direct Output Halt will also cause the axis to exit pressure or force
control. A Closed Loop Halt will not exit pressure or force control.
Releasing a Pressure or Force
Exiting pressure or force control when the actuator is exerting a force against a dead stop
may require careful consideration, especially if it is critical that the force does not
overshoot.
One method is to issue the Hold Current Position (5) command. However, the axis will
now be holding position, and since the Actual Position typically jumps around a bit, it may
cause an undesired increase in the force. Therefore, this may not be a good choice.
Another option is to issue a Move Absolute (20) to move back from the current position.
However, the Actual Velocity typical jumps around a bit, and if it moving in the direction
of increasing force at the instant the Move Absolute command is issued, then the Target
Position must first turn around, meaning that the force may actually increase before
decreasing.
Sometimes, the Open Loop Rate (10) command may work best because it alleviates both
of the aforementioned problems. The Quick Move Absolute (15) will also work well, with
the added benefit that it moves to a known position.
Pressure/Force Control Status Bits
The following status bits give the status of the pressure or force control. These tell you
what the control is doing, and can also be very useful in user programs.
At Pressure/Force
When the axis is in Pressure/Force control or Pressure/Force Limit and the Target
Pressure/Force reaches the Requested Pressure/Force and the Actual Pressure/Force
is within the At Pressure/Force Tolerance window from the Target Pressure/Force, the At
Pressure/Force Status bit will be set. This bit indicates that the ramp is complete and the
axis is at the pressure or force.
Pressure/Force Control
The Pressure/Force Control Status bit indicates that the axis is in closed-loop pressure or
force control.
Pressure/Force Limit Enabled
This bit indicates that pressure/force limit is enabled. If an axis is in pressure or force
control, pressure/force limit will not be active. If the axis exits pressure/force control to
open loop or closed-loop position or velocity control, it will enter pressure/force limit if the
Pressure/Force Limit Enabled bit is on.
Pressure/Force Limited
This bit indicates that pressure/force limit is enabled and the axis is limiting the
pressure/force. If an axis is in pressure or force control, pressure/force limit will not be
active and this bit will not be set.
Pressure/Force Target Generator Bits