11 Troubleshooting
239 Image Area: Invalid command received.
The value written to the Image Area Command register is not supported.
Verify the value written to this register.
240 Image Area: Image downloaded out of sequence.
The image was downloaded improperly. This can happen for the following
reasons:
•
The Current Index register, if written at the start of each write,
may have the wrong value.
•
The Image Data registers were not written to in sequential order.
That is, each consecutive write to the Image Data registers must
either start at the first Image Data register, or must continue
where the last write completed.
•
An individual write extended beyond the end of the Image Area file
(4096 total registers).
•
The total re-assembled downloaded image exceeds 65,536 registers.
To recover from this error, reset the download by writing a zero to the
Current Index register or by writing Reset Image Area (3) to the Image
Area Command register, and then resend the image starting at the
beginning.
241 Image Area: Image uploaded out of sequence
The image was uploaded improperly. This can happen for the following
reasons:
•
The Image Data registers were not read in sequential order. That
is, each consecutive read from the Image Data registers must
either start at the first Image Data register, or must continue
where the last read completed.
•
An individual read extended beyond the end of the Image Area file
(4096 total registers).
•
More than 65,536 total registers have been uploaded.
To recover from this error, write a zero to the Current Index register and
re-upload the image starting at the beginning.
242 Image Area: Invalid Current Index value written.
A non-zero value was written to the Current Index register in the Image
Area. This is only allowed when downloading an image. This register should
not be written to while uploading or at other times.
243 Image Area: Download not allowed in this state.
The Image Data registers cannot be written to while the Image Area is in
this state. Before downloading an image to the Image Area, you should
reset the image area by writing Reset Image Area (3) to the Image Area
Command register. This error can also occur if writes are made after an
Image Area: Image downloaded out of sequence error has occurred.
244 Image Area: Unable to build upload image.
This error will occur if the entire image in the controller is larger than the
maximum size of 65,536 registers and therefore could not be created.
245 Image Area: Unable to apply downloaded image.
The controller was unable to apply the downloaded image. The state of the
controller has not been changed. There are several reasons why the RMC
may be unable to apply a downloaded image. The reason will be listed in the
deltamotion.com