2-Wire Current Transducer

10.2.10. D8 Wiring

Each discrete I/O point on the D8 expansion module is individually configurable in software as

an input or output. Since there is just one input common and one output common, all inputs

must be the same polarity, and all outputs must be the same polarity, but inputs need not be

the same polarity as outputs, that is, outputs can switch high side or low side, and inputs can

be active high or low.
Inputs and outputs are 24Vdc rated, and optically isolated from controller. Since all inputs

share a common connection, there is no isolation between input points. By the same token, all

outputs share a common pin and therefore do not have isolation between outputs.
Wire clamp screws must be tightened to max 7 b-in (0.8Nm).

Pin-Out

Pin

Function

Output

Cmn

Common to one side of all outputs

I/O 0

Input or Output

I/O 1

Input or Output

I/O 2

Input or Output

I/O 3

Input or Output

I/O 4

Input or Output

1140

Delta Computer Systems, Inc.