RMC70/150 and RMCTools User Manual

be used in cases where the Custom Counts register is being modified from an

external device, such as a PLC.


The No Transducer Error bit can still be set by using the No Transducer and Secondary No

Transducer bits in the Custom Error Bits register. Additionally, if the Custom Counts is

NaN, INf, -Inf, the No Transducer error bit will also be set.

Format Details

The Custom Feedback Auto-Fault Mode is selected with bits 0-3. These bits correspond to

the Auto-Fault Mode as shown in the following table:

Bit 3 Bit 2 Bit 1 Bit 0 Value Auto-Fault Mode

0

0

0

0

0

Missed Update

0

0

0

1

1

PROGRAM Mode

0

0

1

0

2

Disabled

See the Custom Feedback Configuration Register for details about the register containing

these bits.

9.2.2.3. Simulator

9.2.2.3.1. Simulate Mode

Type: Axis Parameter Register

RMC70 Address: %MDn.116/0, where n = 12 + the axis number

RMC150 Address: %MDn.116/0, where n = 24 + the axis number

System Tag: _Axis[n].SimulationBits.Simulate

How to Find: Axes Parameters Pane, All tab: Simulate

Data Type: BOOL

Default Value:

False

Description

This parameter puts the axis in simulate mode. See the Simulating Motion topic for

details.
Changing this Parameter
Because this parameter affects motion, the axis must be disabled or in Direct Output

before writing to this parameter. The Enabled and Direct Output Status Bits indicate these

states of the axis. When changing this parameter from RMCTools, the software will

automatically do this for you.

See the Simulator Configuration Register for details about addressing this bit.

9.2.2.3.2. System Gain (Simulator)

Type: Axis Parameter Register

RMC70 Address: %MDn.117, where n = 12 + the axis number

944

Delta Computer Systems, Inc.