3 Controller Features

3.7.2. Controlling Only Pressure or Force

This topic describes how to perform pressure/force control on a pressure-only or force-only

axis. Torque control is identical to pressure or single-input force control. For details on

position-pressure or position-force axes, see the Position-Pressure and Position-Force Control

topic.

Required Hardware

A pressure-only or force-only axis requires the following RMC hardware:

One Control Output

One or Two Analog Inputs

Two analog inputs are required only if you are using two pressure transducers for

differential force feedback.
Note: Any analog input will suffice. The RMC70 does not require the AP2 module for

pressure-only or force-only axes. The RMC150E does not require the pressure

option (indicated as RMC151) for pressure-only or force-only axes. These are only

required for dual-loop axes, such as position-pressure or position-force.


Pressure or Force feedback requires analog feedback transducers (voltage or current).

The input range from the transducer must fall within the RMC supported ranges of ±10V

or 4-20mA. For the best resolution, the feedback should use a large portion of the ±10V

or 4-20mA range.

Define the Axis

The first step for pressure/force control is to define the pressure/force axis. This means

assigning the physical inputs and analog Control Output to an axis in RMCTools.

1. Open the Axis Definitions dialog to define the axes.
2. In order to define the axes as you want them, you may need to first remove the

existing axes and add new axes. Or, you may be able to change an existing axis.

3. Whether you choose to change an existing axis or add a new axis, set the axis to the

following:

Control Axis

1 Input

Input Type: Pressure, Force (single-input), or Force (dual-input)

If you are using a single pressure transducer or load cell for the feedback,

choose Pressure or Force (single-input). If you are using two pressure

transducers for differential force feedback, choose Force (dual-input, diff.).

4. The Axis Definitions dialog will show you exactly which Control Output and analog

input(s) on the RMC will be used for the axis. You can change them if you wish.

5. Click OK on the Axis Definitions dialog. If you are online, these changes will be applied

to the controller. Make sure to update Flash and save your project.

Set Up the Pressure/Force Transducer Parameters

Make sure to set the following pressure/force parameters:

Input Type: Choose Voltage or Current.

Positive Pressure/Force Limit and Negative Pressure/Force Limit: These specify the

pressure/force in which the axis will be allowed to control in. If the Target

Pressure/Force exceeds these values, an error bit will be set and will halt the axis if

the AutoStops are set to do so.

Scale the Pressure/Force