6 Communication

The RMC uses port number 7171 hex (29,041 in decimal) for the Procedure Exist protocol.
A sample program for the Q-Series Procedure Exist method is available on the downloads page

of Delta's website at http://www.deltamotion.com/dloads. This should be used as a starting

point for any Mitsubishi Q-series program using the QJ71E71-100 Ethernet module and an

RMC.
Note:

The RMC can also communicate with the Mitsubishi Q-series PLC via the QJ71MT91 Ethernet

Modbus/TCP module. Modbus/TCP is a complete protocol and therefore using the QJ71MT91

requires less programming than using the QJ71E71-100. Consequently, the QJ71MT91 may be

slightly easier to use with the RMC. The disadvantage is that the QJ71MT91 it is not as widely

used as the QJ71E71-100. A sample program for using the QJ71MT91 is available on the

downloads page of Delta's website.

Configuring the Q-Series

Mitsubishi’s ”Q Corresponding Ethernet Interface Module User's Manual (Basic)” (manual

part number SH (NA)-080009-I, search for 080009 on www.meau.com on the

Downloads>>Manuals section) describes how to set up QJ71E71-100. It is very detailed,

but is very large and may seem difficult. The sections below describe the settings

necessary to use the QJ71E71-100 to communicate with the RMC.
The instructions below are from GX Developer version 8.25B.
1. I/O Assignment Settings
First, set the I/O settings. This is described in section 4.5.1 of the Q Corresponding

Ethernet Interface Module User's Manual (Basic). Notice that there are no Switch settings

to set for this module.
2. Network Parameter Settings
This is described in section 4.6 of the Q Corresponding Ethernet Interface Module User's

Manual (Basic).
In the Project Data List, double-click Network Param, then click MELSEC/Ethernet.

For each QJ71E71-100 module, set the following parameters:

Network Type

Set to Ethernet

Starting I/O

Number

Set this to the head address of the Ethernet module

Network No.

See section 4.6 of the manual (Set to 1)

Total Stations

Group No.

Set to 1

Station No.

Set to 1

Mode

Set to On line

Operational

Settings

Communication data Code: Binary Code
Initial Timing: Do not Wait for Open
IP Address: enter the IP Address of the QJ71E71-100.
Send frame setting: Ethernet(V2.0)
Enable Write at RUN time: cleared
TCP Existence confirmation setting: Use the KeepAlive

Initial

Settings

No settings required here.

Open

Settings

For each RMC you wish to communicate with, you must set up a

paired connection. To do so, on one row, set the following:
Protocol: TCP
Open System: Active

deltamotion.com