beautypg.com

Multiple ethernet/ip i/o connections, Multiple ethernet/ip i/o, Connections – Delta RMC151 User Manual

Page 479

background image

6 Communication

1756-EWEB 4.5.3
1768-ENBT 2.1.0
1768-EWEB 1.2.9
1794-AENT 4.1.1

If you have one of these modules with an older revision, then you should update the

Rockwell Ethernet module firmware, if possible.
Solutions
There are three possible solutions:

1. Update Rockwell Module firmware (recommended)

Update the firmware in the affected Rockwell Ethernet module.

2. Disable Non-Zero DSCP Values in RMCTools

This is not necessary if you followed the recommended solution #1.

In RMCTools, do the following:

a. In the Project tree, expand the Modules folder and double-click the RMC CPU.
b. On the EtherNet/IP page, in the Quality of Service (QoS) section, uncheck

the Enable DiffServ Code Point (DSCP) marking box.

c. Click OK to apply the changes to the RMC. Ensure that the settings are saved

to flash and the module is restarted.

3. Use Older RMC Firmware (not recommended)

Revert the RMC70/150 back to pre-3.41.0 firmware. To obtain old firmware, contact

Delta Technical Support. When updating firmware, you also have the option of backing

up the firmware currently in the module.

6.8.10.6.6. Multiple EtherNet/IP I/O Connections

An RMC can simultaneously have I/O connections open with up to four EtherNet/IP clients

such as PLCs and HMIs. Each connection will share the same I/O data produced by the RMC,

but no more than one I/O connection can be set up to send I/O data to be consumed by the

RMC. Each simultaneous I/O connection must have the same RPI and input data size, and all

connections must use multicast for the RMC’s produced data.
Using multiple I/O connections with an RMC requires that you understand the three types of

connections supported by the RMC:

Input/Output

This connection is bi-directional: the originator (PLC or HMI) produces data consumed

by the RMC and the target (RMC) produces data that is consumed by the originator.

This connection type is also called an Exclusive Owner connection or the controlling

connection. No more than one I/O connection can be an Input/Output connection.

Input Only

For this connection type, only the target (RMC) produces data, which is consumed by

the originator (PLC or HMI). The originator will only send a heartbeat packet,

sometimes at a reduced interval (less frequently than the RPI) used to allow the RMC

to identify when the connection is broken.

Listen Only

This connection type is identical to an Input Only connection type, with a single

exception: a Listen Only connection can only exist when one of the other I/O

connection types has been established. That is, a Listen Only connection cannot be

established until an Input/Output or Input Only connection has been established, and

conversely when the last non-Listen-Only connection has been closed or has timed

out, the Listen Only connection will automatically close as well. This connection type is

the least-frequently used type. This connection is not supported by firmware 3.40.x or

older.

deltamotion.com

459

This manual is related to the following products: