Profibus module, Profibus module (rmc150), Profibus – Delta RMC151 User Manual
Page 694
RMC70/150 and RMCTools User Manual
a. In Channel 0:
•
Choose SSI Output mode.
•
Set the SSI Output Mode to Slave.
•
In the Source of Output Data section, choose the register that
contains the data to be sent. Typically this is a variable.
•
Set the SSI Data Bits to 32.
b. In Channel 1:
•
Choose SSI Register Input mode
•
Set the SSI Input Mode to Standard
•
Set the SSI Termination to ±Data.
•
In the Location to store SSI Data section, choose the register where
the received data will be stored. This must be a variable.
•
Set the SSI Data Bits to 32.
2. Configure the UI/O on the second RMC as follows:
a. In Channel 0:
•
Choose SSI Register Input mode
•
Set the SSI Input Mode to Standard
•
Set the SSI Termination to ±Data.
•
In the Location to store SSI Data section, choose the register where
the received data will be stored. This must be a variable.
•
Set the SSI Data Bits to 32.
b. In Channel 1:
•
Choose SSI Output mode
•
Set the SSI Output Mode to Slave.
•
In the Source of Output Data section, choose the register that
contains the data to be sent. Typically this is a variable.
•
Set the SSI Data Bits to 32.
3. Wire Channel 0 on the first RMC to Channel 0 on the second RMC as shown in RMC150
UI/O Wiring. Wire Channel 1 on the first RMC to Channel 1 on the second RMC.
4. Click OK.
5. The RMCs will automatically send data back and forth to each other.
7.3.11. PROFIBUS Module
7.3.11.1. PROFIBUS Module (RMC150)
The PROFIBUS module for the RMC150 provides PROFIBUS communications. Notice that since
the RMC150E CPU has built-in Ethernet, it is possible to communicate via Ethernet and
PROFIBUS simultaneously.
For details on setting up and using PROFIBUS, see the PROFIBUS Overview topic.
Features
•
PROFIBUS-DP
•
1 Comm Status LED
•
Standard PROFIBUS-DP DB-9 Connector