beautypg.com

Delta RMC151 User Manual

Page 515

background image

6 Communication

Thereby, the values from the selected registers in the RMC70 can be read from and

written to by writing to and reading from the Indirect Data registers.
To set up the Indirect Data Map:

1. Open the Indirect Data Map Editor.
2. In the Register column of the first Indirect Data Map entry, type "%MD8.0" and press

Enter. This will map Axis 0 Status Bits register to the first item in the Indirect Data

Map. Basic mode requires that the first item in the Indirect Data Map contains the Axis

0 Status Bits register.

3. For each of the remaining Indirect Data Map entries 1-7, enter the desired register to

map to each. To do this, click the cell in the Register column, click the ellipsis button
( ), then browse to the desired register.

4. If you wish to add additional read capability, one of the Indirect Data Map registers

should be mapped to the Read Response register. Then, the corresponding register in

the Response Block will return the value of a read from any single register in the

RMC70 at any time. See Read from the RMC70 below.


Example

Requirements
The user would like to read the following registers:

Axis 0 Status Bits

Axis 0 Actual Position

Axis 1 Status Bits

Axis 1 Actual Position

Task 0 Current Step

Task 1 Current Step

In addition, the user would like to read some other registers occasionally.
Implementation

First, PROFIBUS communications requires that Axis 0 Status Bits register

must be in the first Response Block register, which is entry 0 in the Indirect

Data Map.

Second, the Read Response register is needed in order to read other

registers occasionally.

Third, the rest of the registers listed above can be put anywhere in the

remaining Indirect Data Map registers 0-7.

The user chose to set up the Indirect Data Map like this:

Using the Data Blocks

deltamotion.com

495

This manual is related to the following products: