beautypg.com

Communication registers, Ethernet status, Ethernet configuration bits – Delta RMC151 User Manual

Page 1022: Communication registers 2, Ethernet status 2, Ethernet configuration bits 2, Enet.status.linkup, Communication registers 9.2.3.1. ethernet status

background image

RMC70/150 and RMCTools User Manual

Description

This register specifies the rate at which the output is ramped to zero volts due to an Open

Loop Halt or Direct Output Halt. An Open Loop Halt can be initiated by the Open Loop

Halt (2) command or an Auto Stop. A Direct Output Halt can be initiated by the Direct

Output Halt (3) command or an Auto Stop.

9.2.3. Communication Registers

9.2.3.1. Ethernet Status

Type: Communications Register

RMC70 Address: %MD21.10. See Register Map topic for other address formats.

RMC150

Address:

%MD45.10. See Register Map topic for other address formats.

System Tag: _Enet.Status

How to Find: Address Selection Tool → Controller → Communication Settings →

Ethernet

Data Type: DWORD

Accessibility: Read Only


This register indicates the state of various Ethernet communication items.
Bit Tag Name

Description

0

_Enet.Status.LinkUp

Link
True: The Ethernet link is up, and the Ethernet Link/Act LED

will be green (steady or flashing).
False: The Ethernet link is down.

1

_Enet.Status.100Mbps 100 Mbps

True: The Ethernet speed is 100Mbps
False: The Ethernet speed is 10Mbps

2

_Enet.Status.FullDuplex Full Duplex

True: The Ethernet is full-duplex.
False: The Ethernet is half-duplex.

4-7 _Enet.Status.IPState

Current IP Address State
0: Static Method, but an unusable address is assigned (e.g.

0x00000000)
1: IP Address assigned and in use
2:
IP Address assigned, but disabled due to duplicate detected
3:
IP Address assigned, but still doing Address Collision

Detection
4:
BOOTP: Still querying, no address yet assigned
5:
DHCP: Still querying, no address yet assigned

9.2.3.2. Ethernet Configuration Bits