beautypg.com

Delta RMC151 User Manual

Page 626

background image

RMC70/150 and RMCTools User Manual


Notice that the RMC’s I and Q data should generally not be accessed directly but should

instead go through the DPRD_DAT and DPWR_DAT SFCs in order to ensure that the data

is always handled as a consistent block.

Reading and Writing Record Data from the S7

Use the Data Records to read from or write to any location in the RMC. Record Data reads

and writes can be performed while the cyclic data exchange is occurring. The maximum

Record Data read or write length is 2048 32-bit registers (8192 bytes).

Fixed Data Records

Data Records 7-255 correspond to the register files 7 -255 in the RMC, as listed in the

RMC150 Register Map and RMC70 Register Map. Reads and writes of Data Records 7-

255 will begin at element 0 of the file. Fixed Data Records are useful for accessing plot

data, the Variable Table, and even the command area.

Custom Data Records

The locations of Data Records 1000-1003 can be specified in the PROFINET Settings

Page in RMCTools. This overcomes the Fixed Data Records limitations of starting at

element 0. Custom Data Records are useful for accessing any location in the RMC.

Reading and Writing Record Data
To read and write Record Data, use the RDREC (SFB52) and WRREC (SFB53) system

function blocks.

1. Insert the SFB52 (RDREC) or SFB53 (WRREC).
2. At the top of the SFB, type a name of a new Data Block (DB). If it does not exist, after

pressing Enter, STEP 7 will prompt to create a new one. Choose Yes.

3. Wire the EN input to turn on as required by your application.
4. Wire the REQ input so that it will turn on for one scan to trigger the read or write. This

can be done with a one-shot.

5. The ID must be set to the diagnostic address of the first slot/subslot of the RMC. In

the RDREC Example below, the value DW#16#7FB is the hexadecimal equivalent of

the diagnostic address 2043, also shown in step 10 above in the Hardware setup slot

table.

6. Index is the Data Record number to read from or write to.
7. Set MLen or Len to four times the number of 32-bit registers to be sent or received.

The maximum length is 8192 bytes (2048 32-bit registers).

8. Set Record to the Data Block that contains the source or destination data. You must

define this Data Block. The contents of the Data Block should match the data area of

the RMC.

9. Wire the Valid, Busy, Error, and Status outputs as required by your application.

RDREC Example

606

Delta Computer Systems, Inc.

This manual is related to the following products: