Delta RMC151 User Manual
Page 1098
RMC70/150 and RMCTools User Manual
sample at which the
plot trigger
occurred. Only
applies for Plot
State > 0.
F35:14-
15
17949-
17951
D17948-
D17950
-
%MD35.14-
15
-
-
Reserved
F35:16-
31
17953-
17983
D17952-
D17981
REAL
%MD35.16-
31
DWORD Read/Write Plot Data Sets 0-15
Addresses
Files %MDn:16-31
contain the
Addresses for plot
Data Sets 0-15.
Bits 0-11 Element
Bits 12-23 File
Plot 4
F36:0
18433
D18432 REAL
%MD36.0 UDINT not
directly
Plot Flags
These bits should
not be accessed
directly.
0 Reserved (Write
Only)
1 Trigger (Write
only)
2 Rearm (Write
Only)
3 Read Active
(Read Only)
4 Trigger Enabled
(Read Only)
F36:1
18435
D18434 REAL
%MD36.1 UDINT Read/Write Plot Samples (e.g.
1000)
F36:2
18437
D18436 REAL
%MD36.2 REAL
Read/Write Plot Sample Period
(seconds)
F36:3
18439
D18438 REAL
%MD36.3 DINT
Read/Write Plot Axis Owner
0-3, -1 = none
F36:4
18441
D18440 REAL
%MD36.4 REAL
Read/Write Plot Trigger Position
%, 0-100, -1 =
auto rearm
F36:5
18443
D18442 REAL
%MD36.5 UDINT Read/Write Plot Trigger Type
0-
7
Trigger Type
(0=none,
1=motion
command)
8-
23
Depends on
trigger type
Motion
Commands:
1078
Delta Computer Systems, Inc.