The Commanded Axes specifies which axes to issue the command to.

Click the Command Axes button and choose the axes you wish to issue the command

to. For example, selecting Axis 0 and Axis 1 will make the command be issued to both

axes.

The Default Axis and Use Expression options are typically used only in advanced

applications. If you choose Default Axis, the command will be issued to the same axis

as the Start Task command was issued to. The Use Expression option can be used to

programmatically select the commanded axes.

Click OK to close the commanded axes list.

Important: A maximum of one non-immediate command per axis can be issued in a

single step. If you try to issue more than one command to an axis per step, the verify will

report an error and you will not be able to download the programs.
Choosing a Link Type

1. Click the down-arrow in the Link Type box and click the link type you want.
2. If the link type has a condition, enter it according to the table below:

Link

Type

To enter a Link condition:

Immed N/A

Jump N/A

Delay Type a number, or click the ellipsis button to choose a tag.

Wait

For

Click the ellipsis button to open the Link Condition Wizard.

Cnd

Jump

Click the ellipsis button to open the Link Condition Wizard.

End N/A

3. If you chose Jump, Delay, or CndJump, enter the step to jump to in the Jump To

box(es). You can enter a step number, "Next", or a step label.

Adding A Comment

On the Step Editor toolbar, click the Edit Step Comment button. Or, right-click in

the space below the step number and choose Edit Step Comment.

Type a comment and click Save.

Adding A Label

On the Step Editor toolbar, click the Edit Label button. Or, right-click in the space

below the step number and choose Edit Label.

Type a label and click Save.

Adding Local Variable Declarations
If you are using the Expression (113) command, you can also define local variables for

use in the step. See Local Variables in Expressions for details.

On the toolbar, click the Declarations button.

Copy/Paste
The Step Editor fully supports copy and paste. You can copy and paste any section of a

step, entire steps, multiple steps, etc. The copy and paste also works between instances

of RMCTools.
Printing
To print the currently open user program, on the Step Editor toolbar, click the Print

button . Or, on the File menu, choose Print.