beautypg.com

Ethernet/ip performance considerations, E ethernet/ip i/o performance – Delta RMC151 User Manual

Page 480

background image

RMC70/150 and RMCTools User Manual

Configuring Multiple Connections

To establish multiple I/O connections with an RMC, you simply create I/O connections

from each originator (PLC or HMI) to the RMC as you would normally. However, you must

obey the following rules in order for all of the connections to be successful:

All connections must be set up to use multicast (not unicast) for target-to-originator

(T->O) packets.

All connections must use the same RPI value. See the Requested Packet Interval

(RPI) section of the Setting up an EtherNet/IP I/O Connection topic for details on the

minimum RPI supported based on the number of open connections.

All connections must have the target-to-orginator (T->O) data size set the same.

No more than one of the connections can be an Input/Output connection.

Listen Only connections will not connect until at least one Input/Output or Input Only

connection has been established.

Each connection must be set up correctly for its desired connection type, as described

in detail in Setting up an EtherNet/IP I/O Connection.

Using Multiple Connections

When performing communications with multiple EtherNet/IP I/O connections, the

Input/Output connection (or controlling connection) behaves as normal. The Input Only

and Listen Only connections can only view the data from the RMC—they can't write to the

RMC. If the Sync Register is being used, then the first register in the Input Data is the

Sync register and is of no use for the Input Only devices.

6.8.10.6.7. EtherNet/IP Performance Considerations

There are several areas to consider with regard to EtherNet/IP Performance:

General Recommendations

Considerations for RMC EtherNet/IP Performance

Considerations for Master EtherNet/IP Performance

Considerations for Network Performance

General Recommendations

The following recommendations will improve the performance and determinism of the

network in general.

Always use unicast I/O connections instead of multicast whenever possible. Notice that

Allen-Bradley products only supported multicast connections prior to RSLogix 5000

v18.

Do not use a lower RPI than you need. Usually an RPI of 10 ms or 20 ms is sufficient.

Lowering the RPI will increase the load on every Ethernet component in the system,

and beyond a certain point has no benefit. For example, if the RPI is lower than the

scan time of the controlling PLC, then additional packets will not benefit the system.

Never use hubs or other half-duplex switchgear. This will introduce collisions, which

greatly reduce the scalability and determinism of a network.

When using a multicast connection, never connect the EtherNet/IP I/O network to a

general purpose network, except through a router. The multicast traffic on the

EtherNet/IP network will be noticed by your IT department. Conversely, glitches on

the general purpose network could affect your factory network. If only unicast I/O

connections are used, then connecting to a general purpose network through a switch

may be acceptable in some applications.

460

Delta Computer Systems, Inc.

This manual is related to the following products: