beautypg.com

Position-pressure and position-force control, Controlling both position and pressure, Controlling both position and force – Delta RMC151 User Manual

Page 170: E position-pressure and position-force control

background image

RMC70/150 and RMCTools User Manual

Pressure/Force Target Generator Done bit
This bit indicates that the Target Pressure or Target Force has reached the Requested

Pressure/Force. If the ramp is interrupted, e.g. due to a halt, the done bit will not be

set because the commanded motion was not completed. Notice that this bit does not

indicate whether the Actual Pressure or Actual Force has reached the Requested

Pressure/Force.
Pressure/Force Target Generator State A and B bits
B

A Description

0

0

The target generator is complete

0

1

Pressure/Force is accelerating

1

0

Constant

1

1

Pressure/Force is decelerating

3.7.3. Position-Pressure and Position-Force Control

This topic describes position-pressure and position-force control. For information on pressure

control only or force control only, see the Pressure/Force Limit topic.
Pressure/Force Control or Pressure/Force Limit can be used on position-pressure or position-

force control axes. Position-torque is identical to or position-force with a single-input force, or

position-pressure.

Required Hardware

A position-pressure or position-force axis requires the following RMC hardware:

Pressure-Enabled Controller

This is the term for an RMC that supports dual-loop control, such as position-

pressure or position-force.

o

RMC70: Requires the AP2 module.

o

RMC150E: Requires the pressure option (denoted as RMC151). This must

be specified when ordering the RMC.

o

One Control Output

o

One Position Input

This can be any type of position feedback supported by the RMC.

o

One or Two Analog Inputs

Two analog inputs are required only if you are using two pressure transducers for

differential force feedback.

Pressure or Force feedback requires analog feedback transducers (voltage or current).

The input range from the transducer must fall within the RMC supported ranges of ±10V

or 4-20mA. For the best resolution, the feedback should use a large portion of the ±10V

or 4-20mA range.

Define the Axis

The first step for pressure/force control is to define the axis. This means assigning the

physical inputs and analog Control Output to an axis in RMCTools.

1. Open the Axis Definitions dialog to define the axes.
2. In order to define the axes as you want them, you may need to first remove the

existing axes and add new axes. Or, you may be able to change an existing axis.

3. Whether you choose to change an existing axis or add a new axis, set the axis to the

following:

150

Delta Computer Systems, Inc.

This manual is related to the following products: