Connection Type

The RMC supports three types of I/O connections:

Input/Output

This connection is bidirectional: the originator (PLC or HMI) produces data consumed

by the RMC and the target (RMC) produces data that is consumed by the originator.

This connection type is also called an Exclusive Owner connection or the controlling

connection. Each RMC can have no more than one Input/Output connection open at a

time.

Input Only

For this connection type, only the target (RMC) produces data, which is consumed by

the originator (PLC or HMI). The originator will only send a heartbeat packet,

sometimes at a reduced interval (less frequently than the RPI) used to allow the RMC

to identify when the connection is broken.

Listen Only

This connection type is identical to an Input Only connection type, with one exception:

a Listen Only connection can only exist when one of the other I/O connection types

has been established. That is, a Listen Only connection cannot be established until an

Input/Output or Input Only connection has been established, and conversely when the

last non-Listen-Only connection has been closed or has timed out, the Listen Only

connection will automatically close as well. This connection type is the least-frequently

used. This connection type is not supported by RMC firmware 3.40.x or older.

Of these three, the Input/Output connection type is by far the most commonly used. The

other two are generally only used when multiple I/O connections are used. See the

Multiple EtherNet/IP I/O Connections topic for details.
When using the RMC’s EDS file in your EtherNet/IP configuration tool, you should be able

to select the I/O connection type from a list. Notice that in addition to the three listed

above, you may also see Input/Output with Config and Input Only with Config.

These connection types are generally not used. For details on these connection types, see

the Configuration Data section below. If you are using a Generic EDS File (as required by

RSLogix 5000 as of this writing), see the Using a Generic EDS File section below.

Requested Packet Interval (RPI)

EtherNet/IP I/O sends data between the communicating devices at the Requested

Packet Interval (RPI). The RPI is configured in the EtherNet/IP controller (for example,

RSLogix 5000), not in RMCTools. The RMC supports the following RPIs, based on the

number of simultaneous I/O connections established (see the Multiple EtherNet/IP I/O

Connections topic):

I/O

Connections

Minimum RPI

Typical RPI

Maximum RPI

1 (typical)

2 ms

20 ms

10,000 ms

2

3 ms

20 ms

10,000 ms

3

4 ms

20 ms

10,000 ms

4

4 ms

20 ms

10,000 ms


Also, the RPI must be both an integer number of milliseconds and a multiple of the RMC’s

Loop Time. For example, an RPI of 9 ms would not be allowed for a loop time of 2 ms or 4

ms, but would be for 1 ms or lower loop times.
Delta recommends using the slowest RPI that meets the requirements of your application

in order to reduce network requirements. See the EtherNet/IP I/O Performance topic for

more details.

Multicast vs. Point-to-Point (Unicast)

446

Delta Computer Systems, Inc.