D.3.5 status (pressure/force) bit map – Delta RMC101 User Manual
Page 888
RMC100 and RMCWin User Manual
D-26
Not Regulating
Pressure
0
0
Increasing Pressure
0
1
Constant Pressure
1
0
Decreasing Pressure
1
1
Bit 1 - Regulating Pressure Bit
This bit is set when a pressure axis is actively controlling pressure. You may use this bit to
determine when the axis has crossed into pressure mode out of position mode. This bit is not
latched, and will clear as soon as the axis leaves pressure mode.
Bit 0 - At Pressure
This bit will be set when the difference between the Actual Pressure and Command Pressure is
less than the value in the At Pressure field; it is not latched.
Note:
The control program can monitor this bit to determine when an axis has reached the
commanded pressure.
D.3.5 Status (Pressure/Force) Bit Map
The axis Status word contains 16 bits of information about the status of the axis. This
hexadecimal table provides an easy way to convert hexadecimal numbers to bit patterns.