3. If you are creating a new PROFIBUS-DP network, you must create a new network and add a
master device to the network.
• On the File menu, click New. If you have multiple networks installed you will need to then select
the network type: select PROFIBUS. If you are not given the option of selecting PROFIBUS,
you may not have installed the PROFIBUS driver for SyCon.
• On the Insert menu, click Master. Move the cursor to the top device slot in the window area (the
cursor will change to an arrow with an ’r;M’ next to it), and click to place the master device.
• In the Insert Master dialog box, select the desired master and click the Add>> button. Enter the
station address, and click OK.
• On the Settings menu, click Bus Parameter.
• In the Bus Parameter dialog box, set the Baud Rate to the desired rate. The RMC is capable of
speeds up to 12000kBits/s (12MBaud); check the rates supported by your master and other
slaves. Click OK.
4. Add the DELT1630.GSD file to your configuration program’s GSD database.
• You must first have an open PROFIBUS project file.
• On the File menu, click Copy GSD.
• In the Open dialog box, navigate to the directory where the DELT1630.GSD file is located (by
default it is installed in the main RMCWin directory), select that file and click Open.
• NOTE: This will not add the bitmap file. If you wish to use the bitmap file; copy the
DELTRMCN.BMP file to the Fieldbus\Profibus\BMP directory under the SyCon directory (by
default, the total path will be C:\Program Files\Hilscher GmbH\SyCon\Fieldbus\Profibus\BMP).
5. Add a Delta RMC Family slave device to the network.
• On the Insert menu, click Slave. Move the cursor to the next available device slot in the window
area (the cursor will change to an arrow with an S next to it), and click to place the device.
• In the Insert Slave dialog box, click Delta RMC Family, and then click the Add>> button. Enter
the station address, and click OK.
6. Configure the RMC Slave Device. This involves selecting the correct configuration module for
your RMC module and application. Refer to the sub-topic Determining the Appropriate GSD
Configuration Module in the PROFIBUS Configuration topic for details on selecting the correct
configuration module.
• Right-click on the RMC slave device icon, and click Slave Configuration from the shortcut
menu.
• In the Slave Configuration dialog box, from the list of order numbers, select the configuration
module you selected in the previous steps.
• Click Append Module.
• You may change the I Addr. and O Addr. fields for the added module to set the offsets of the
data.
• Click OK.