beautypg.com

Differential gain, C.2.10 differential gain – Delta RMC101 User Manual

Page 797

background image

Appendix C: Parameter Field Reference

C-27

that you set the Integral Gain to a value of at least 50.

Integral Gain is defined as:


Integral Gain = millivolts per 10240 counts of accumulated Position Error


Integral Drive is defined as:


Integral Drive = Integral Gain x Accumulated Counts / 10240

Note:

The actual drive output may be reduced based on the values of the Extend Feed Forward

and Retract Feed Forward .

Why Bother?
Integral Gain should be used to compensate for the fact that loads may vary, valves are non-
linear and the axis may have trouble getting to the Command Position without Integral Gain.

C.2.10 Differential Gain

Default: 0
Range: 0 to 65535

The Differential Gain field is used to apply a gain based on the rate of change between the target
and actual positions. There are two ways to view this.

First, this is a gain multiplied by the current rate of change in the position error. The differential
drive, in millivolts is computed as follows:

where:

K

d

=

Differential Gain in mV/[pos-units/ms]

E

0

=

position error this control loop in position units

E

1

=

position error last control loop in position units

LoopTime =

RMC Control Loop Time in ms (1 or 2)


A second equivalent way of viewing this parameter is as the gain multiplied by the velocity error.
When looked at from this angle, the above equations become the following:

This manual is related to the following products: