RMC100 and RMCWin User Manual

4-46

• Issue Open Loop (O) commands with small positive and negative drives to see if the cylinder

goes in the right direction.

• If the cylinder moves in the wrong direction, the wiring to the drive may be swapped, or Reverse

Drive mode can be selected in the Config word.

• Check the deadband. This system has a very small deadband, approx 5 millivolts, so we will not

worry about it.

• Set the gains and feed forwards to zero and issue a Set Parameters (P) command.

• Double-click the Axis 0 Auto Stop word (in the Parameters field).

o

Set the Overdrive, Integrator Windup and Overdrive bits to Status only. Note that is possible

only on systems where safety is not important.

o

Set the proportional gain to a small value, such as 5. Issue a Set Parameters (P) command.

o

Set the Plot Time for Axis 0 to 4.

o

Now make a move. The tuning process will consist of repeatedly making moves. To easily make

repeated moves, use Stored Commands.

o

To edit and view the Stored Commands, click Stored Command Editor on the Stored

Commands

menu. The following window appears:

o

For example, ALT-1 on axis 0 will issue a Go cmd to 4000 at a speed of 2 in/sec, with

acceleration rates of 10 in/(sec*sec). These are common initial values for moving hydraulic
systems. Thes values are editable from this window.

o

To use the stored commands, click on any Axis 0 field, then press e.g. ALT-1 to move to 4