Ethernet 5.2

Communications

5-141

Plot Type Registers:
The plot type registers can be read or written. The values that are read indicate the extra plot
information in the current graph. The values written to these registers tell the controller which
extra plot information to obtain on the next plot. For these registers, the following values are used:

• 0: Extra position precision
• 1: Command and Command Value

• 2: Event Step and Link Value
• 3: Raw Transducer Counts

• 4: Internal Target and Actual Speeds
• 5: Integral Drive

For more information on these four types of plot information, see Selecting the Data to Plot and
Reading Plots from the Communication Module.

Omron

Address

Register Description

D02624

Axis 0 plot type

D02625

Axis 1 plot type

D02626

Axis 2 plot type

D02627

Axis 3 plot type

D02628

Axis 4 plot type

D02629

Axis 5 plot type

D02630

Axis 6 plot type

D02631

Axis 7 plot type

Digital (Discrete) I/O Registers:
These registers indicate the current state of the digital inputs and outputs. These registers may
only be read; writes will be ignored, as this product does not support forcing inputs or outputs.

The Omron PLCs and the RMC use the same bit numbering. Therefore, bit numbers in the table
below use 0 for the least-significant bit and 15 for the most-significant bit:

Omron

Address

Register Description

D02632

CPU Digital Inputs 0 and 1 in LSBs of low
byte, Outputs 0 and 1 in LSBs of high byte

D02633

Unused

D02634

Unused

D02635

Sensor Digital I/O Inputs 0-15